Installation of the Essential TR Contactor
TASK 24-34-55-400-001-A
Installation of the Essential TR Contactor
1. Reason for the Job
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 24-34-55-860-050-A
Subtask 24-34-55-410-050-A
[Rev.10 from 2021]
2026.03.31 23:23:34 UTC
Installation of the Essential TR Contactor
1. Reason for the Job
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE |
| No specific | Torque wrench: range to between 0.30 and 0.27 m.daN (26.55 and 23.89 lbf.in ) ![]() |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 125 | LATERAL AVIONIC COMPARTMENT |
| 812, 822 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-24-00-710-001-A | Operational Check of Emergency Generating System |
Subtask 24-34-55-860-050-A
A. Aircraft Maintenance Configuration
(1) Make sure that the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE is in position at the access doors 812 and 822.
(2) Make sure that the access doors 812 and 822 are open.
(3) In the avionics compartment, make sure that the access panel of the AC/DC emergency power center 106VU and BATTERY power center 105VU are open.
Subtask 24-34-55-865-051-A (1) Make sure that the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE is in position at the access doors 812 and 822.
(2) Make sure that the access doors 812 and 822 are open.
(3) In the avionics compartment, make sure that the access panel of the AC/DC emergency power center 106VU and BATTERY power center 105VU are open.
B. Make sure that this(these) circuit breaker(s) is(are) open, safetied and tagged:
4. Procedure| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 105VU | ELEC/CSM/G /EV AUTO/SPLY | 7XE | C01 |
| 106VU | CSM/G /EV/MAN/SPLY | 6XE | B04 |
| 106VU | ESS TR/SPLY | 4PE | C01 |
| 122VU | ELEC/CNTOR/ESS/DC BUS/TIE | 3PC | W26 |
| 123VU | AC ESS/BUS ON/BUS 1 | 1XC | AC12 |
| 123VU | AC ESS/BUS ON/BUS 2 | 2XC | AC01 |
CAUTION:
MAKE SURE THAT THE CONTACTOR LOCATING PIN IS CORRECTLY ENGAGED IN ITS RECESS LOCATED IN ONE POWER TERMINAL.
THIS PREVENTS DAMAGE TO THE LOCATING PIN WHEN YOU APPLY THE TORQUE.
Subtask 24-34-55-420-050-A A. Installation of the Contactor
(1) Install the contactor (5) in position on the tapped barrels (6) of the connecting base (1).
(2) TORQUE the captive screws (3) to between 0.30 and 0.27 m.daN (26.55 and 23.89 lbf.in )
.
(3) Remove the CAP-BLANKING from each electrical connector and receptacle.
(4) Make sure that all the electrical connections are clean and in the correct condition.
(5) Connect the connector (4) on the contactor (5).
Subtask 24-34-55-865-052-A (1) Install the contactor (5) in position on the tapped barrels (6) of the connecting base (1).
(2) TORQUE the captive screws (3) to between 0.30 and 0.27 m.daN (26.55 and 23.89 lbf.in )
. (3) Remove the CAP-BLANKING from each electrical connector and receptacle.
(4) Make sure that all the electrical connections are clean and in the correct condition.
(5) Connect the connector (4) on the contactor (5).
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 24-34-55-710-050-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 105VU | ELEC/CSM/G /EV AUTO/SPLY | 7XE | C01 |
| 106VU | CSM/G /EV/MAN/SPLY | 6XE | B04 |
| 106VU | ESS TR/SPLY | 4PE | C01 |
| 122VU | ELEC/CNTOR/ESS/DC BUS/TIE | 3PC | W26 |
| 123VU | AC ESS/BUS ON/BUS 1 | 1XC | AC12 |
| 123VU | AC ESS/BUS ON/BUS 2 | 2XC | AC01 |
C. Operational Test of the Emergency Generation System
(1) Do an operational test of the Emergency Generation System (Ref. AMM TASK 24-24-00-710-001).
5. Close-up(1) Do an operational test of the Emergency Generation System (Ref. AMM TASK 24-24-00-710-001).
Subtask 24-34-55-410-050-A
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) In the avionics compartment, close the access panels of the AC/DC emergency power center 106VU and the BATTERY power center 105VU.
(3) Close the access doors 812 and 822.
(4) Remove the access platform(s).
(1) Make sure that the work area is clean and clear of tools and other items.
(2) In the avionics compartment, close the access panels of the AC/DC emergency power center 106VU and the BATTERY power center 105VU.
(3) Close the access doors 812 and 822.
(4) Remove the access platform(s).
Essential TR Contactor