Removal of the Emergency Generator Line Contactor (EMER GLC)
TASK 24-24-55-000-001-A
Removal of the Emergency Generator Line Contactor (EMER GLC)
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 24-24-55-941-051-A
[Rev.10 from 2021]
2026.03.31 23:22:43 UTC
Removal of the Emergency Generator Line Contactor (EMER GLC)
WARNING:
MAKE SURE THAT NO AC OR DC POWER IS CONNECTED TO THE AIRCRAFT ELECTRICAL CIRCUITS.
THERE IS A RISK OF ELECTROCUTION IF THE AC OR DC POWER STAYS CONNECTED.
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| No specific | AR | WARNING NOTICE(S) |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 125 | LATERAL AVIONIC COMPARTMENT |
| 812, 822 |
| REFERENCE | DESIGNATION |
|---|---|
Subtask 24-24-55-941-051-A
A. Safety Precautions
(1) In the cockpit, on the overhead panel 35VU, make sure that these pushbutton switches are released:
(4) Put a WARNING NOTICE(S) on the access door 121AL to tell persons not to connect the external power connector.
Subtask 24-24-55-010-050-A (1) In the cockpit, on the overhead panel 35VU, make sure that these pushbutton switches are released:
- BAT 1, BAT 2,
- GEN 1(2), APU GEN,
- EXT PWR.
- 21VU (EMER ELEC PWR),
- 35VU (ELEC).
(4) Put a WARNING NOTICE(S) on the access door 121AL to tell persons not to connect the external power connector.
B. Get access to the avionics compartment.
(1) Put an ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE at the avionics compartment doors 812 and 822.
(2) Open the access doors 812 and 822.
Subtask 24-24-55-865-050-A (1) Put an ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE at the avionics compartment doors 812 and 822.
(2) Open the access doors 812 and 822.
C. Open, safety and tag this(these) circuit breaker(s):
Subtask 24-24-55-010-052-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| 105VU | ELEC/CSM/G /EV AUTO/SPLY | 7XE | C01 |
| 106VU | ESS TR/SPLY | 4PE | C01 |
| 122VU | ELEC/CNTOR/ESS/DC BUS/TIE | 3PC | W26 |
| 123VU | AC ESS/BUS ON/BUS 1 | 1XC | AC12 |
| 123VU | AC ESS/BUS ON/BUS 2 | 2XC | AC01 |
D. Get Access
(1) In the avionics compartment, remove the access panel (1) from the AC/DC emergency power center 106VU.
4. Procedure(1) In the avionics compartment, remove the access panel (1) from the AC/DC emergency power center 106VU.
CAUTION:
MAKE MATCH MARKS ON ALL THE ELECTRICAL WIRES BEFORE YOU DISCONNECT THEM. INCORRECT CONNECTION OF WIRES WILL CAUSE DAMAGE TO EQUIPMENT.
Subtask 24-24-55-020-050-A A. Removal of the Contactor
(1) Disconnect the wires (6) from the contactor (7).
(2) Remove the 6 screws (5) and washers (4).
(3) Remove the power supply wires (3).
(4) Loosen the 4 nuts (2).
(5) Hold the contactor (7).
(6) Remove the 4 nuts (2).
(7) Remove the contactor (7).
(1) Disconnect the wires (6) from the contactor (7).
(2) Remove the 6 screws (5) and washers (4).
(3) Remove the power supply wires (3).
(4) Loosen the 4 nuts (2).
(5) Hold the contactor (7).
(6) Remove the 4 nuts (2).
(7) Remove the contactor (7).
Contactor