Removal of the GCU-APU
TASK 24-23-34-000-001-A
Removal of the GCU-APU
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 24-23-34-860-051-A ** ON A/C NOT FOR ALL
Subtask 24-23-34-020-050-A ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.03.31 23:22:26 UTC
Removal of the GCU-APU
CAUTION:
MAKE SURE THAT NO AC OR DC POWER IS CONNECTED TO THE AIRCRAFT ELECTRICAL CIRCUITS.
THERE IS A RISK OF DAMAGE TO EQUIPMENT DURING ITS REMOVAL/ INSTALLATION IF THE AC OR DC POWER STAYS CONNECTED.
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 18M (59 FT) - ADJUSTABLE |
| No specific | AR | CAP - BLANKING |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| No specific | AR | WARNING NOTICE(S) |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 121 | AVIONICS COMPARTMENT |
| 811 |
| REFERENCE | DESIGNATION |
|---|---|
Subtask 24-23-34-860-051-A ** ON A/C NOT FOR ALL
A. Safety Precautions
(1) In the cockpit, on the overhead panel 25VU and 35VU, make sure these pushbutton switches are released:
Subtask 24-23-34-865-050-A ** ON A/C NOT FOR ALL (1) In the cockpit, on the overhead panel 25VU and 35VU, make sure these pushbutton switches are released:
- START,
- APU GEN.
- 25VU (APU),
- 35VU (ELEC).
B. Open, safety and tag this(these) circuit breaker(s):
Subtask 24-23-34-010-050-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 122VU | ELEC/GEN1/OFF/BTC1 SPLY | 5XU | T28 |
| 122VU | ELEC/APU/GCU | 6XS | Y25 |
C. Get Access
(1) Put an ACCESS PLATFORM 18M (59 FT) - ADJUSTABLE at the access door 811 of the avionics compartment.
(2) Open the access door 811.
4. Procedure(1) Put an ACCESS PLATFORM 18M (59 FT) - ADJUSTABLE at the access door 811 of the avionics compartment.
(2) Open the access door 811.
Subtask 24-23-34-020-050-A ** ON A/C NOT FOR ALL
A. Removal of the GCU
(1) Loosen the 2 knurled nuts (1).
(2) Lower the 2 knurled nuts (1) to disengage the 2 studs (2).
(3) Carefully pull the handle (3) of the GCU (4) until the GCU is disconnected from the rack receptacle (5).
(4) Remove the GCU from the rack (6).
(5) Put CAP - BLANKING on the rack receptacle (5) and the GCU connector.
(1) Loosen the 2 knurled nuts (1).
(2) Lower the 2 knurled nuts (1) to disengage the 2 studs (2).
(3) Carefully pull the handle (3) of the GCU (4) until the GCU is disconnected from the rack receptacle (5).
(4) Remove the GCU from the rack (6).
(5) Put CAP - BLANKING on the rack receptacle (5) and the GCU connector.
APU Generator Control Unit (GCU)