W DOC AIRBUS | AMM A320F

Installation of the Temperature Selector


TASK 21-63-11-400-001-A
Installation of the Temperature Selector


ZONE: 210
FIN: 27HK
FIN: 28HK
FIN: 29HK
1. Reason for the Job
Self explanatory
2. Job Set-up Information
 A. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
210
CKPT,FWD COMPT BHD TO FLT COMPT BULKHEAD
 B. Referenced Information
REFERENCE
DESIGNATION
TASK 21-63-00-710-004-A
Operational Test of the Cockpit and Cabin Temperature Control with CFDS/MCDU
3. Job Set-up
Subtask 21-63-11-865-051-A
A. Make sure that this(these) circuit breaker(s) is(are) open, safetied and tagged:
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
49VUAIR COND/FLOW/CTL &/IND11HBD07
** ON A/C NOT FOR ALL
49VUAIR BLEED/ENG 1/CTL3HA1D12
49VUAIR BLEED/ENG 1/MONG2HA1D11
** ON A/C ALL
49VUAIR BLEED/X FEED/VALVE/BAT2HVD13
49VUAIR COND/RAM/AIR/INLET1HZD10
** ON A/C NOT FOR ALL
49VUAIR BLEED/ENG 2/MONG3HA2D12
49VUAIR BLEED/ENG 1/CTL2HA1D11
** ON A/C NOT FOR ALL
122VUAIR COND/FLOW/CTL AND IND/22HBV21
122VUAIR COND/ZONE TEMP CTL/28VDC/SYS24HKV20
122VUAIR COND/ZONE TEMP CTL/28VDC/SYS13HKV19
122VUAIR COND/ZONE TEMP CTL/115VAC/SYS22HKV18
122VUAIR COND/ZONE TEMP CTL/115VAC/SYS11HKV17
** ON A/C NOT FOR ALL
122VUAIR BLEED/ENG 2/CTL3HA2Z23
122VUAIR BLEED/ENG 2/MONG2HA2Z22
** ON A/C ALL
122VUAIR BLEED/X FEED VALVE/NORM1HVZ20
** ON A/C NOT FOR ALL
122VUAIR BLEED/ENG 1/MONG3HA1Z23
122VUAIR BLEED/ENG 2/CTL2HA2Z22
4. Procedure
Subtask 21-63-11-420-050-A
A. Install the temperature selector:
   (1) Install the potentiometer (5). Put the locating stud (6) at the top opposite the black mark (7).
   (2) Install the washer (8).
   (3) Install the nut (9) and tighten it.
   (4) Align the knob (10) with the flat of the shaft.
   (5) Push the knob until it is fully engaged.
   (6) Moderatily tighten the two screws (11).
   (7) Remove the blanking cap from the electrical connector (4) and make sure that the electrical connector is in the correct condition.
   (8) Connect the electrical connector (4).
   (9) Put the panel 30VU (2) in its housing.
   (10) Turn the 4 QAD fasteners (1) one quarter turn.
5. Close-up
Subtask 21-63-11-865-052-A
A. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
49VUAIR COND/FLOW/CTL &/IND11HBD07
** ON A/C NOT FOR ALL
49VUAIR BLEED/ENG 1/CTL3HA1D12
49VUAIR BLEED/ENG 1/MONG2HA1D11
** ON A/C ALL
49VUAIR BLEED/X FEED/VALVE/BAT2HVD13
49VUAIR COND/RAM/AIR/INLET1HZD10
** ON A/C NOT FOR ALL
49VUAIR BLEED/ENG 2/MONG3HA2D12
49VUAIR BLEED/ENG 1/CTL2HA1D11
** ON A/C NOT FOR ALL
122VUAIR COND/FLOW/CTL AND IND/22HBV21
122VUAIR COND/ZONE TEMP CTL/28VDC/SYS24HKV20
122VUAIR COND/ZONE TEMP CTL/28VDC/SYS13HKV19
122VUAIR COND/ZONE TEMP CTL/115VAC/SYS22HKV18
122VUAIR COND/ZONE TEMP CTL/115VAC/SYS11HKV17
** ON A/C NOT FOR ALL
122VUAIR BLEED/ENG 2/CTL3HA2Z23
122VUAIR BLEED/ENG 2/MONG2HA2Z22
** ON A/C ALL
122VUAIR BLEED/X FEED VALVE/NORM1HVZ20
** ON A/C NOT FOR ALL
122VUAIR BLEED/ENG 1/MONG3HA1Z23
122VUAIR BLEED/ENG 2/CTL2HA2Z22
Subtask 21-63-11-710-050-A
B. Do an operational test of the cockpit and cabin temperature control (Ref. AMM TASK 21-63-00-710-004).
Subtask 21-63-11-942-050-A
C. Make sure that the work area is clean and clear of tools and other items.