Removal of the Pack-Inlet Pressure Sensor


TASK 21-61-16-000-001-A
Removal of the Pack-Inlet Pressure Sensor


WARNING: MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE. HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
NOTE: The procedure is the same for the pack inlet-pressure sensors 16HH and 36HH.
FIN: 16HH ** ON A/C NOT FOR ALL
FIN: 36HH ** ON A/C NOT FOR ALL
1. Reason for the Job
Self explanatory
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
FOR [16HH] (P1 PRESS INL SENSOR)
No specific
AR
CAP - BLANKING
No specific
AR
PLUG - BLANKING
FOR [36HH] (P2 PRESS INL SENSOR)
No specific
AR
CAP - BLANKING
No specific
AR
PLUG - BLANKING
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
FOR [16HH] (P1 PRESS INL SENSOR)
191KB
FOR [36HH] (P2 PRESS INL SENSOR)
192KB
 C. Referenced Information
REFERENCE
DESIGNATION
TASK 24-41-00-861-002-A
Energize the Aircraft Electrical Circuits from the External Power
TASK 24-41-00-861-002-A-01
Energize the Aircraft Electrical Circuits from the APU
TASK 24-41-00-861-002-A-02
Energize the Aircraft Electrical Circuits from Engine 1(2)
TASK 53-35-13-000-002-A
Removal of the Quick-Release Access Panels from the Belly Fairing Structure
3. Job Set-up
Subtask 21-61-16-861-050-A ** ON A/C NOT FOR ALL
A. Energize the aircraft electrical circuits (Ref. AMM TASK 24-41-00-861-002).
Subtask 21-61-16-865-052-A ** ON A/C NOT FOR ALL
B. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
FOR FIN: 16HH (P1 PRESS INL SENSOR)
122VUAIR COND/PACK TEMP/CTL SYS1/1/115VAC1HHX22
122VUAIR COND/PACK TEMP/CTL SYS1/1/28VDC3HHX21
122VUAIR COND/PACK TEMP CTL SYS2/1/28VDC4HHY19
122VUAIR COND/PACK TEMP CTL SYS2/1/115VAC2HHY18
FOR FIN: 36HH (P2 PRESS INL SENSOR)
122VUAIR COND/PACK TEMP/CTL SYS1/2/115VAC21HHW22
122VUAIR COND/PACK TEMP/CTL SYS1/2/28VDC23HHW21
122VUAIR COND/PACK TEMP CTL SYS2/2/28VDC24HHY21
122VUAIR COND/PACK TEMP CTL SYS2/2/115VAC22HHY20
Subtask 21-61-16-010-050-A ** ON A/C NOT FOR ALL
C. Get Access
   (1) Remove the access panel (Ref. AMM TASK 53-35-13-000-002),
     (a) FOR [16HH] (P1 PRESS INL SENSOR)
191KB.
     (b) FOR [36HH] (P2 PRESS INL SENSOR)
192KB.
4. Procedure
Subtask 21-61-16-020-051-B ** ON A/C NOT FOR ALL
A. Removal of the Pack Inlet Pressure Sensor
   (1) FOR [16HH] (P1 PRESS INL SENSOR)
     (a) Disconnect the electrical connector (5).
     (b) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
     (c) Disconnect the pressure sense line (1).
     (d) Put the PLUG-BLANKING in each disconnected line end.
     (e) Remove the nut (9), the washer (8), the bolt (6) and disconnect the bonding strap (7).
     (f) Remove the screws (4) and the washers (3).
     (g) Remove the pack-inlet pressure sensor (10) together with the clamps (2).
     (h) Remove the clamps (2).
   (2) FOR [36HH] (P2 PRESS INL SENSOR)
     (a) Disconnect the electrical connector (24).
     (b) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
     (c) Disconnect the pressure sense line (21).
     (d) Put the PLUG-BLANKING in each disconnected line end.
     (e) Remove the nut (25), the washer (27), the bolt (25) and disconnect the bonding strap (26).
     (f) Remove the screws (23) and the washers (22).
     (g) Remove the pack-inlet pressure sensor (29) together with the clamps (31).
     (h) Remove the clamps (31).