Installation of the Compressor Overheat - Temperature Sensor
TASK 21-61-12-400-001-A
Installation of the Compressor Overheat - Temperature Sensor
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Consumable Materials
C. Work Zones and Access Panels
D. Expendable Parts
E. Referenced Information
3. Job Set-up
Subtask 21-61-12-860-050-A ** ON A/C NOT FOR ALL
Subtask 21-61-12-420-050-A ** ON A/C NOT FOR ALL
Subtask 21-61-12-410-051-A ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.04.02 06:11:37 UTC
Installation of the Compressor Overheat - Temperature Sensor
WARNING:
MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
NOTE: The procedure is the same for the compressor overheat temperature sensors 15HH and 35HH.
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | Torque wrench: range to between 1.0 and 0.8 m.daN (88.50 and 70.80 lbf.in ) ![]() |
| REFERENCE | DESIGNATION |
|---|---|
| (Material No.03FAB1) | Mineral Oil base Grease-- Vaseline or Petrolatum - |
| (Material No.14QDB1) | Wire-Locking Dia: 0.5 mm (0.020 inch) CRES Nickel Alloy - |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| FOR [15HH] (SENSOR-COMPRESSOR OVHT) | |
| 191KB | |
| FOR [35HH] (SENSOR-COMPRESSOR OVHT) | |
| 192KB | |
| FIG.ITEM | DESIGNATION | IPC-CSN |
|---|---|---|
| 3 | PACKING | AIPC 21-61-03-08-050 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 21-61-00-710-001-A | Operational Test of the Pack Temperature-Control System |
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 53-35-13-000-002-A | Removal of the Quick-Release Access Panels from the Belly Fairing Structure |
| TASK 53-35-13-400-002-A | Installation of the Quick-Release Access Panels on the Belly Fairing Structure |
Subtask 21-61-12-860-050-A ** ON A/C NOT FOR ALL
A. Aircraft Maintenance Configuration
(1) Make sure that the aircraft electrical circuits are energized (Ref. AMM TASK 24-41-00-861-002).
(2) Make sure that the access panel/s is are removed (Ref. AMM TASK 53-35-13-000-002).
(a) FOR [15HH] (SENSOR-COMPRESSOR OVHT)
(b) FOR [35HH] (SENSOR-COMPRESSOR OVHT)
Subtask 21-61-12-865-055-A ** ON A/C NOT FOR ALL (1) Make sure that the aircraft electrical circuits are energized (Ref. AMM TASK 24-41-00-861-002).
(2) Make sure that the access panel/s is are removed (Ref. AMM TASK 53-35-13-000-002).
(a) FOR [15HH] (SENSOR-COMPRESSOR OVHT)
(b) FOR [35HH] (SENSOR-COMPRESSOR OVHT)
B. Make sure that this(these) circuit breaker(s) is(are) open, safetied and tagged:
4. Procedure| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 15HH (SENSORCOMPRESSOR OVHT) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| FOR FIN: 35HH (SENSORCOMPRESSOR OVHT) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
Subtask 21-61-12-420-050-A ** ON A/C NOT FOR ALL
A. Installation of the Compressor Overheat-Temperature Sensor
(1) Make sure that the parts retained from the removed component are clean and in the correct condition.
(2) Make sure that the removed packing (3) is in a good condition. If necessary replace the AIPC 21-61-03-08-050 PACKING (3).
(3) Remove the blanking plugs from the disconnected line ends.
(4) Clean the component interfaces and the adjacent area.
(5) Apply a small quantity of Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) to the contact faces of the compressor overheat- temperature sensor (1) and to the packing (3).
(6) Put the packing (3) in position on the compressor overheat-temperature sensor (1).
(7) Install the compressor overheat-temperature sensor (1) in the pipe assembly (4).
(8) TORQUE the compressor overheat-temperature sensor (1) to between 1.0 and 0.8 m.daN (88.50 and 70.80 lbf.in )
.
(9) Wipe clean the excess Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) from the compressor overheat-temperature sensor (1) and safety with14QDB1 Wire-Locking Dia: 0.5 mm (0.020 inch) CRES Nickel Alloy - .
(10) Remove the blanking caps and connect the electrical connector (2).
(11) Make sure that the work area is clean and clear of tools and other items.
Subtask 21-61-12-865-056-A ** ON A/C NOT FOR ALL (1) Make sure that the parts retained from the removed component are clean and in the correct condition.
(2) Make sure that the removed packing (3) is in a good condition. If necessary replace the AIPC 21-61-03-08-050 PACKING (3).
(3) Remove the blanking plugs from the disconnected line ends.
(4) Clean the component interfaces and the adjacent area.
(5) Apply a small quantity of Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) to the contact faces of the compressor overheat- temperature sensor (1) and to the packing (3).
(6) Put the packing (3) in position on the compressor overheat-temperature sensor (1).
(7) Install the compressor overheat-temperature sensor (1) in the pipe assembly (4).
(8) TORQUE the compressor overheat-temperature sensor (1) to between 1.0 and 0.8 m.daN (88.50 and 70.80 lbf.in )
. (9) Wipe clean the excess Mineral Oil base Grease-- Vaseline or Petrolatum - (Material No.03FAB1) from the compressor overheat-temperature sensor (1) and safety with
(10) Remove the blanking caps and connect the electrical connector (2).
(11) Make sure that the work area is clean and clear of tools and other items.
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-61-12-710-050-A ** ON A/C NOT FOR ALL 5. Close-up| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 15HH (SENSORCOMPRESSOR OVHT) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| FOR FIN: 35HH (SENSORCOMPRESSOR OVHT) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
Subtask 21-61-12-410-051-A ** ON A/C NOT FOR ALL
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access panel/s (Ref. AMM TASK 53-35-13-400-002).
(a) FOR [15HH] (SENSOR-COMPRESSOR OVHT)
(b) FOR [35HH] (SENSOR-COMPRESSOR OVHT)
Subtask 21-61-12-862-050-A ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access panel/s (Ref. AMM TASK 53-35-13-400-002).
(a) FOR [15HH] (SENSOR-COMPRESSOR OVHT)
(b) FOR [35HH] (SENSOR-COMPRESSOR OVHT)
Compressor Overheat - Temperature Sensor