W DOC AIRBUS | AMM A320F

Removal of the Duct Temperature Sensor


TASK 21-58-11-000-001-A
Removal of the Duct Temperature Sensor


WARNING: MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE. HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
WARNING: DO NOT TOUCH THE COMPONENT UNTIL IT IS SUFFICIENTLY COOL TO PREVENT BURNS.
FIN: 115HW ** ON A/C NOT FOR ALL
1. Reason for the Job
Self explanatory
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
1
ACCESS PLATFORM 2M (6 FT)
No specific
AR
CAP - BLANKING
No specific
AR
PLUG - BLANKING
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
No specific
1
WARNING NOTICE(S)
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
191KB
 C. Referenced Information
REFERENCE
DESIGNATION
TASK 24-41-00-861-002-A
Energize the Aircraft Electrical Circuits from the External Power
TASK 24-41-00-861-002-A-01
Energize the Aircraft Electrical Circuits from the APU
TASK 24-41-00-861-002-A-02
Energize the Aircraft Electrical Circuits from Engine 1(2)
TASK 53-35-13-000-002-A
Removal of the Quick-Release Access Panels from the Belly Fairing Structure
3. Job Set-up
Subtask 21-58-11-861-050-A ** ON A/C NOT FOR ALL
A. Energize the aircraft electrical circuits
(Ref. AMM TASK 24-41-00-861-002).
Subtask 21-58-11-865-050-A ** ON A/C NOT FOR ALL
B. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C NOT FOR ALL
49VUAIR BLEED/X FEED/VALVE/BAT2HVD13
49VUAIR COND/TEMP CTL/SYS 1 CHAN B/28VDC52HHD08
** ON A/C NOT FOR ALL
49VUAIR BLEED/ENG 1/CTL3HA1D12
49VUAIR BLEED/ENG 1/MONG2HA1D11
** ON A/C NOT FOR ALL
49VUAIR BLEED/ENG 2/MONG3HA2D12
49VUAIR BLEED/ENG 1/CTL2HA1D11
** ON A/C NOT FOR ALL
121VUIGGS/CTRL7YAN28
** ON A/C NOT FOR ALL
121VUIGGS/CTRL7YAP28
** ON A/C NOT FOR ALL
122VUCSAS / CTRL1HWU17
122VUAIR COND/TEMP CTL SYS 1/CHAN A/115VAC49HHX22
122VUAIR COND/TEMP CTL SYS 1/CHAN A/28VDC51HHX21
122VUAIR COND/TEMP CTL SYS 1/CHAN B/115VAC50HHY18
122VUAIR BLEED/X FEED VALVE/NORM1HVZ20
** ON A/C NOT FOR ALL
122VUAIR BLEED/ENG 2/CTL3HA2Z23
122VUAIR BLEED/ENG 2/MONG2HA2Z22
** ON A/C NOT FOR ALL
122VUAIR BLEED/ENG 1/MONG3HA1Z23
122VUAIR BLEED/ENG 2/CTL2HA2Z22
Subtask 21-58-11-941-050-A ** ON A/C NOT FOR ALL
C. Safety Precautions
   (1) On the panel 30VU, make sure that:
  • The APU BLEED pushbutton switch is in the off position (the ON legend is off).
  • The ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF legends are on).
     (a) Put a WARNING NOTICE(S) in position to tell persons not to operate these pushbutton switches.
   (2) On the HP ground connector put a warning notice in position to tell persons not to supply the ground air.
Subtask 21-58-11-010-050-A ** ON A/C NOT FOR ALL
D. Get Access
   (1) Put an ACCESS PLATFORM 2M (6 FT) in position at the zone 191.
   (2) Remove the access panel 191KB (Ref. AMM TASK 53-35-13-000-002).
4. Procedure
Subtask 21-58-11-020-050-A ** ON A/C NOT FOR ALL
A. Removal of the Temperature Sensor
F Temperature Sensor (115HW) ** ON A/C NOT FOR ALL
   (1) Disconnect the electrical connector (3).
   (2) Put a CAP - BLANKING on the disconnected electrical connector (3).
   (3) Remove and discard the locking wire from the temperature sensor (2).
   (4) Remove the temperature sensor (2) and the O-ring (1).
   (5) Discard the O-ring (1).
   (6) Put PLUG - BLANKING on the disconnected line ends.
[Rev.10 from 2021] 2026.04.02 06:11:34 UTC