Pressure Drop Test of the Reheater
TASK 21-52-00-780-001-A
Pressure Drop Test of the Reheater
Referenced from TSM.
This procedure is only applicable to reheaters with the P/N 755A0000-04 and previous.
It is not applicable to reheaters with the P/N's 755A0000-04 Amendment A or subsequent.
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Consumable Materials
C. Expendable Parts
D. Referenced Information
3. Job Set-up
Subtask 21-52-00-861-056-A Subtask 21-52-00-865-061-A
Subtask 21-52-00-410-054-A
[Rev.10 from 2021]
2026.04.02 06:11:24 UTC
Pressure Drop Test of the Reheater
WARNING:
MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
1. Reason for the JobReferenced from TSM.
This procedure is only applicable to reheaters with the P/N 755A0000-04 and previous.
It is not applicable to reheaters with the P/N's 755A0000-04 Amendment A or subsequent.
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Consumable Materials
| REFERENCE | DESIGNATION |
|---|---|
| (Material No.14QFB1) | Wire-Locking Dia: 0.8 mm CRES Nickel Alloy - |
| FIG.ITEM | DESIGNATION | IPC-CSN |
|---|---|---|
| 2 | PACKING | AIPC 21-61-03-05-040 |
| 2 | PACKING | AIPC 21-61-83-13-040 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 12-33-21-618-001-A-01 | Pre-conditioning through the HP Ground Connection |
| TASK 12-33-21-618-001-A-02 | Pre-conditioning with the APU |
| TASK 21-52-00-100-002-A | Remove Reheater for In Shop Cleaning |
| TASK 21-52-31-000-001-A | Removal of the Reheater |
| TASK 21-52-31-400-001-A | Installation of the Reheater |
| TASK 21-61-00-710-001-A | Operational Test of the Pack Temperature-Control System |
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 31-60-00-860-001-A | EIS Start Procedure |
| TASK 31-60-00-860-002-A | EIS Stop Procedure |
| TASK 49-00-00-860-005-A | APU Start by External Power |
| TASK 49-00-00-860-005-A-01 | APU Start by Batteries |
| TASK 49-00-00-860-006-A | APU Shutdown by External Power |
| TASK 49-00-00-860-006-A-01 | APU Shutdown by Batteries |
| TASK 49-00-00-860-008-A | APU Start by External Power |
| TASK 49-00-00-860-008-A-01 | APU Start by Batteries |
| TASK 49-00-00-860-009-A | APU Shutdown by External Power (131-9(A)) |
| TASK 49-00-00-860-009-A-01 | APU Shutdown by Batteries (131-9(A)) |
| TASK 53-35-13-000-002-A | Removal of the Quick-Release Access Panels from the Belly Fairing Structure |
| TASK 53-35-13-400-002-A | Installation of the Quick-Release Access Panels on the Belly Fairing Structure |
Subtask 21-52-00-861-056-A Subtask 21-52-00-865-061-A
B. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-52-00-941-051-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 10HM3 (REHEATER) | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 11HM3 (REHEATER) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
C. Safety Precautions
(a) Make sure that the APU BLEED and the ENG BLEED/1(2) pushbutton switches are released.
(b) Put a warning notice in position to tell persons not to operate these pushbutton switches.
(2) On the HP ground connector put a warning notice in position to tell persons not to supply the ground air.
Subtask 21-52-00-010-056-A NOTE: You must obey these precautions before you carry out any removal or installation tasks.
(1) On the panel 30VU: (a) Make sure that the APU BLEED and the ENG BLEED/1(2) pushbutton switches are released.
(b) Put a warning notice in position to tell persons not to operate these pushbutton switches.
(2) On the HP ground connector put a warning notice in position to tell persons not to supply the ground air.
D. Get Access
(1) Remove the access panel/s (Ref. AMM TASK 53-35-13-000-002).
(a) FOR [10HM3] (REHEATER)
4. Procedure(1) Remove the access panel/s (Ref. AMM TASK 53-35-13-000-002).
(a) FOR [10HM3] (REHEATER)
- 191KB.
- 192KB.
WARNING:
DO NOT TOUCH THE COMPONENT UNTIL IT IS SUFFICIENTLY
COOL TO PREVENT BURNS.
Subtask 21-52-00-480-050-A A. Installation of the Test Equipment
(1) Disconnect the electrical connector (4).
(2) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
(4) Put the packings (2) in position on the LOCALLY MANUFACTURED - ADAPTER (6).
(6) Connect the HOSE - BLEED to the adaptors (6) and to the VALVE - 3 WAYS.
(7) Connect a GAGE 10 BAR (145 PSI) - PRESSURE to the three-way valve (9).
Subtask 21-52-00-865-067-A (1) Disconnect the electrical connector (4).
(2) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
WARNING:
USE PROTECTIVE GOGGLES AND GLOVES WHEN YOU REMOVE OR INSTALL LOCKWIRE. EACH TIME YOU CUT LOCKWIRE, REMOVE AND DISCARD IT IMMEDIATELY. LOOSE LOCKWIRE CAN CUT YOU OR MAKE YOU BLIND, AND/OR CAN CAUSE DAMAGE.
(3) Remove and discard the lockwire and remove the temperature sensor (5), the sealing plug (1) and the packings (2). (4) Put the packings (2) in position on the LOCALLY MANUFACTURED - ADAPTER (6).
NOTE: You can use modified threaded plugs to make the adaptors.
The maximum 37.0 mm (1.4567 in.) dimension is necessary.
(5) Put the adaptors (6) in position in the pressure tapping port (3) and in the temperature sensor port (10). The maximum 37.0 mm (1.4567 in.) dimension is necessary.
(6) Connect the HOSE - BLEED to the adaptors (6) and to the VALVE - 3 WAYS.
(7) Connect a GAGE 10 BAR (145 PSI) - PRESSURE to the three-way valve (9).
NOTE: Make sure that the pressure gauge (8) can measure to 40 psi (2.7579 bar).
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-52-00-860-059-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 10HM3 (REHEATER) | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 11HM3 (REHEATER) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
C. Do the start procedure of the APU:
Subtask 21-52-00-860-051-A ** ON A/C NOT FOR ALL D. Aircraft Maintenance Configuration
(1) Do the EIS start procedure (Ref. AMM TASK 31-60-00-860-001).
(a) On the ECAM upper display unit (DU) the warning AIR PACK REGUL. FAULT will be displayed. You must ignore this warning.
(2) On the panel 30VU:
(a) Make sure that the PACK FLOW selector is at the NORM position.
(b) Turn the COCKPIT, FWD CABIN and the AFT CABIN temperature selectors to the COLD position.
(c) Make sure that the X BLEED selector is in the AUTO position and that the HOT AIR pushbutton switch is off (shows OFF legend on).
(d) Select the respective air condition pack:
1 FOR [10HM3] (REHEATER)
a On the panel 30VU push the PACK 1 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 1 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 1 bleed pressure.
d Wait for 5 minutes to allow the pack 1 outlet temperature and the pack 1 bleed pressure to stabilize.
2 FOR [11HM3] (REHEATER)
a On the panel 30VU push the PACK 2 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 2 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 2 bleed pressure.
d Wait for 5 minutes to allow the pack 2 outlet temperature and the pack 2 bleed pressure to stabilize.
Subtask 21-52-00-860-051-B ** ON A/C NOT FOR ALL (1) Do the EIS start procedure (Ref. AMM TASK 31-60-00-860-001).
(a) On the ECAM upper display unit (DU) the warning AIR PACK REGUL. FAULT will be displayed. You must ignore this warning.
(2) On the panel 30VU:
(a) Make sure that the PACK FLOW selector is at the NORM position.
(b) Turn the COCKPIT, FWD CABIN and the AFT CABIN temperature selectors to the COLD position.
(c) Make sure that the X BLEED selector is in the AUTO position and that the HOT AIR pushbutton switch is off (shows OFF legend on).
(d) Select the respective air condition pack:
1 FOR [10HM3] (REHEATER)
a On the panel 30VU push the PACK 1 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 1 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 1 bleed pressure.
d Wait for 5 minutes to allow the pack 1 outlet temperature and the pack 1 bleed pressure to stabilize.
NOTE: Start the test measurement as soon as possible.
2 FOR [11HM3] (REHEATER)
a On the panel 30VU push the PACK 2 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 2 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 2 bleed pressure.
d Wait for 5 minutes to allow the pack 2 outlet temperature and the pack 2 bleed pressure to stabilize.
NOTE: Start the test measurement as soon as possible.
D. Aircraft Maintenance Configuration
(1) Do the EIS start procedure (Ref. AMM TASK 31-60-00-860-001).
(a) On the ECAM upper display unit (DU) the warning AIR PACK REGUL. FAULT will be displayed. You must ignore this warning.
(2) On the panel 30VU:
(a) Make sure that on the ECON FLOW switch the ON legend is not shown.
(b) Turn the COCKPIT, FWD CABIN and the AFT CABIN temperature selectors to the COLD position.
(c) Make sure that the X BLEED selector is in the AUTO position and that the HOT AIR pushbutton switch is off (shows OFF legend on).
(d) Select the respective air condition pack:
1 FOR [10HM3] (REHEATER)
a On the panel 30VU push the PACK 1 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 1 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 1 bleed pressure.
d Wait for 5 minutes to allow the pack 1 outlet temperature and the pack 1 bleed pressure to stabilize.
2 FOR [11HM3] (REHEATER)
a On the panel 30VU push the PACK 2 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 2 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 2 bleed pressure.
d Wait for 5 minutes to allow the pack 2 outlet temperature and the pack 2 bleed pressure to stabilize.
Subtask 21-52-00-780-050-A (1) Do the EIS start procedure (Ref. AMM TASK 31-60-00-860-001).
(a) On the ECAM upper display unit (DU) the warning AIR PACK REGUL. FAULT will be displayed. You must ignore this warning.
(2) On the panel 30VU:
(a) Make sure that on the ECON FLOW switch the ON legend is not shown.
(b) Turn the COCKPIT, FWD CABIN and the AFT CABIN temperature selectors to the COLD position.
(c) Make sure that the X BLEED selector is in the AUTO position and that the HOT AIR pushbutton switch is off (shows OFF legend on).
(d) Select the respective air condition pack:
1 FOR [10HM3] (REHEATER)
a On the panel 30VU push the PACK 1 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 1 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 1 bleed pressure.
d Wait for 5 minutes to allow the pack 1 outlet temperature and the pack 1 bleed pressure to stabilize.
NOTE: Start the test measurement as soon as possible.
2 FOR [11HM3] (REHEATER)
a On the panel 30VU push the PACK 2 pushbutton switch to the on position (shows FAULT and OFF legends off).
b On the ECAM control panel push the BLEED pushbutton switch.
c On the ECAM lower DU monitor the pack 2 outlet temperature ( 15 deg.C (59.00 deg.F)) and the pack 2 bleed pressure.
d Wait for 5 minutes to allow the pack 2 outlet temperature and the pack 2 bleed pressure to stabilize.
NOTE: Start the test measurement as soon as possible.
E. Pressure Drop Test
(2) Make a note of the upstream pressure (Y) as shown on the pressure gauge (8).
(3) Open the three-way valve (9) to the downstream pressure (X) position.
(4) Make a note of the downstream pressure (X) as shown on the pressure gauge (8).
(5) Subtract the downstream pressure (X) from the upstream pressure (Y) to give you the pressure difference.
(6) If the pressure difference is:
(a) below 1.5 psi (0.1034 bar) no corrective action is required.
(b) between 1.5 psi (0.1034 bar) and 2.0 psi (0.1379 bar) you must clean the reheater (11) (Ref. AMM TASK 21-52-00-100-002).
(c) more than 2.0 psi (0.1379 bar) you must replace the reheater (11) (Ref. AMM TASK 21-52-31-000-001) and (Ref. AMM TASK 21-52-31-400-001).
Subtask 21-52-00-860-052-A NOTE: To avoid ice build up at the turbine outlet it is recommended that the test does not last more than 10 minutes.
(1) Open the three-way valve (9) to the upstream pressure (Y) position. (2) Make a note of the upstream pressure (Y) as shown on the pressure gauge (8).
(3) Open the three-way valve (9) to the downstream pressure (X) position.
(4) Make a note of the downstream pressure (X) as shown on the pressure gauge (8).
(5) Subtract the downstream pressure (X) from the upstream pressure (Y) to give you the pressure difference.
(6) If the pressure difference is:
(a) below 1.5 psi (0.1034 bar) no corrective action is required.
(b) between 1.5 psi (0.1034 bar) and 2.0 psi (0.1379 bar) you must clean the reheater (11) (Ref. AMM TASK 21-52-00-100-002).
(c) more than 2.0 psi (0.1379 bar) you must replace the reheater (11) (Ref. AMM TASK 21-52-31-000-001) and (Ref. AMM TASK 21-52-31-400-001).
F. Aircraft Maintenance Configuration
(1) Do the stop procedure of the APU:
Subtask 21-52-00-865-068-A (1) Do the stop procedure of the APU:
- (Ref. AMM D/O 49-00-00-86) or,
- (Ref. AMM TASK 49-00-00-860-006) or,
- (Ref. AMM TASK 49-00-00-860-009),
G. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-52-00-080-050-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 10HM3 (REHEATER) | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 11HM3 (REHEATER) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
H. Removal of the Test Equipment
(1) Carefully disconnect the hoses (7), the three-way valve (9) and the pressure gauge (8).
(3) Clean the component interfaces and the adjacent area.
(4) Put a new AIPC 21-61-03-05-040 PACKING (2) or AIPC 21-61-83-13-040 PACKING (2) on the sealing plug (1) and on the temperature sensor (5).
(5) Install the sealing plug (1) in the pressure tapping port (3) and the pressure sensor (5) in the pressure sensor port (10).
(6) TORQUE the sealing plug (1) to between 0.55 and 0.45 m.daN (48.67 and 39.82 lbf.in )
.
(7) TORQUE the temperature sensor (5) to between 1.0 and 0.5 m.daN (88.50 and 44.25 lbf.in )
.
(8) Safety the sealing plug (1) and the temperature sensor (5) with14QFB1 Wire-Locking Dia: 0.8 mm CRES Nickel Alloy - .
(9) Remove the blanking caps from the disconnected electrical connectors.
(10) Make sure that all the electrical connections are clean and in the correct condition.
(11) Connect the electrical connector (4)
(12) Make sure that the work area is clean and clear of tools and other items.
Subtask 21-52-00-865-082-A (1) Carefully disconnect the hoses (7), the three-way valve (9) and the pressure gauge (8).
NOTE: You must slowly disconnect the hoses (7) to release any residual pressure which may be present in the test system.
(2) Remove the adaptors (6) and discard the packings (2). (3) Clean the component interfaces and the adjacent area.
(4) Put a new AIPC 21-61-03-05-040 PACKING (2) or AIPC 21-61-83-13-040 PACKING (2) on the sealing plug (1) and on the temperature sensor (5).
(5) Install the sealing plug (1) in the pressure tapping port (3) and the pressure sensor (5) in the pressure sensor port (10).
(6) TORQUE the sealing plug (1) to between 0.55 and 0.45 m.daN (48.67 and 39.82 lbf.in )
. (7) TORQUE the temperature sensor (5) to between 1.0 and 0.5 m.daN (88.50 and 44.25 lbf.in )
. (8) Safety the sealing plug (1) and the temperature sensor (5) with
(9) Remove the blanking caps from the disconnected electrical connectors.
(10) Make sure that all the electrical connections are clean and in the correct condition.
(11) Connect the electrical connector (4)
(12) Make sure that the work area is clean and clear of tools and other items.
I. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-52-00-860-053-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 10HM3 (REHEATER) | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 11HM3 (REHEATER) | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
J. Pre-conditioning and Leak Check
(1) Do the pre-conditioning through the APU (Ref. AMM TASK 12-33-21-618-001) or the HP ground connector (Ref. AMM TASK 12-33-21-618-001).
(2) Do a check for leaks at the sealing plug (1) and at the temperature sensor (5).
Leaks are not permitted.
(3) Stop the pre-conditioning.
Subtask 21-52-00-710-053-A 5. Close-up(1) Do the pre-conditioning through the APU (Ref. AMM TASK 12-33-21-618-001) or the HP ground connector (Ref. AMM TASK 12-33-21-618-001).
(2) Do a check for leaks at the sealing plug (1) and at the temperature sensor (5).
Leaks are not permitted.
(3) Stop the pre-conditioning.
Subtask 21-52-00-410-054-A
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel/s (Ref. AMM TASK 53-35-13-400-002).
(a) FOR [10HM3] (REHEATER)
Subtask 21-52-00-862-055-A (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel/s (Ref. AMM TASK 53-35-13-400-002).
(a) FOR [10HM3] (REHEATER)
- 191KB.
- 192KB.
Differential Pressure Test Connection Points