General Visual Inspection of the Bellows between the Pack Outlet and the Mixer Unit
TASK 21-52-00-200-011-A
General Visual Inspection of the Bellows between the Pack Outlet and the Mixer Unit
referenced from TSM
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 21-52-00-861-061-A Subtask 21-52-00-865-073-A
Subtask 21-52-00-210-058-A
Subtask 21-52-00-865-085-A
[Rev.10 from 2021]
2026.04.02 06:11:25 UTC
General Visual Inspection of the Bellows between the Pack Outlet and the Mixer Unit
WARNING:
MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
1. Reason for the Jobreferenced from TSM
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| FOR [10HM] (PACK 1-AIR CONDITIONING) | |
| 191BB | |
| FOR [11HM] (PACK 2-AIR CONDITIONING) | |
| 192FB | |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 21-52-00-200-013-A | Detailed Inspection of the Pack Downstream Check-Valve Flappers |
| TASK 24-42-00-861-001-A | Energize the Ground Service Network from the External Power |
| TASK 53-35-13-000-002-A | Removal of the Quick-Release Access Panels from the Belly Fairing Structure |
| TASK 53-35-13-400-002-A | Installation of the Quick-Release Access Panels on the Belly Fairing Structure |
Subtask 21-52-00-861-061-A Subtask 21-52-00-865-073-A
B. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-52-00-010-070-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 10HM (PACK 1AIR CONDITIONING) | |||
| 49VU | AIR COND/FLOW/CTL &/IND1 | 1HB | D07 |
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 11HM (PACK 2AIR CONDITIONING) | |||
| 122VU | AIR COND/FLOW/CTL AND IND/2 | 2HB | V21 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
C. Get Access
(1) Remove the access panels:
(Ref. AMM TASK 53-35-13-000-002).
(a) FOR [10HM] (PACK 1-AIR CONDITIONING)
(b) FOR [11HM] (PACK 2-AIR CONDITIONING)
4. Procedure(1) Remove the access panels:
(Ref. AMM TASK 53-35-13-000-002).
(a) FOR [10HM] (PACK 1-AIR CONDITIONING)
(b) FOR [11HM] (PACK 2-AIR CONDITIONING)
Subtask 21-52-00-210-058-A
A. General Visual Inspection of the Bellows
(1) In the air-conditioning pack bay do a general visual inspection of the bellows (1).
(2) Make sure that the bellows (1) have no damage and are correctly installed.
(3) If one or both of the bellows are damaged,
5. Close-up(1) In the air-conditioning pack bay do a general visual inspection of the bellows (1).
(2) Make sure that the bellows (1) have no damage and are correctly installed.
(3) If one or both of the bellows are damaged,
- do the detailed inspection of the pack downstream check-valve flappers (Ref. AMM TASK 21-52-00-200-013).
- replace the damaged bellows.
Subtask 21-52-00-865-085-A
A. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-52-00-410-068-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 10HM (PACK 1AIR CONDITIONING) | |||
| 49VU | AIR COND/FLOW/CTL &/IND1 | 1HB | D07 |
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/TEMP CTL/SYS 1 CHAN B/28VDC | 52HH | D08 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/115VAC | 1HH | X22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/1/28VDC | 3HH | X21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/28VDC | 4HH | Y19 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/1/115VAC | 2HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/115VAC | 49HH | X22 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN A/28VDC | 51HH | X21 |
| 122VU | AIR COND/TEMP CTL SYS 1/CHAN B/115VAC | 50HH | Y18 |
| ** ON A/C NOT FOR ALL | |||
| FOR FIN: 11HM (PACK 2AIR CONDITIONING) | |||
| 122VU | AIR COND/FLOW/CTL AND IND/2 | 2HB | V21 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/115VAC | 21HH | W22 |
| 122VU | AIR COND/PACK TEMP/CTL SYS1/2/28VDC | 23HH | W21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/28VDC | 24HH | Y21 |
| 122VU | AIR COND/PACK TEMP CTL SYS2/2/115VAC | 22HH | Y20 |
| ** ON A/C NOT FOR ALL | |||
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/115VAC | 53HH | W22 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN A/28VDC | 55HH | W21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/28VDC | 56HH | Y21 |
| 122VU | AIR COND/TEMP CTL SYS 2/CHAN B/115VAC | 54HH | Y20 |
B. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panels (Ref. AMM TASK 53-35-13-400-002).
(a) FOR [10HM] (PACK 1-AIR CONDITIONING)
(b) FOR [11HM] (PACK 2-AIR CONDITIONING)
(3) Remove the WARNING NOTICE(S).
Subtask 21-52-00-862-060-A (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panels (Ref. AMM TASK 53-35-13-400-002).
(a) FOR [10HM] (PACK 1-AIR CONDITIONING)
(b) FOR [11HM] (PACK 2-AIR CONDITIONING)
(3) Remove the WARNING NOTICE(S).
C. De-energize the ground service network
Pipe Assembly between Pack Outlet and the Mixer Unit - Component Location