Removal of the Duct Temperature Sensor (Inlet Duct)
TASK 21-43-14-000-002-A
Removal of the Duct Temperature Sensor (Inlet Duct)
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 21-43-14-861-050-A ** ON A/C NOT FOR ALL Subtask 21-43-14-865-051-A ** ON A/C NOT FOR ALL
Subtask 21-43-14-020-050-A ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.04.02 06:48:20 UTC
Removal of the Duct Temperature Sensor (Inlet Duct)
WARNING:
MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
FIN: 3HC ** ON A/C NOT FOR ALL
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | AR | ACCESS PLATFORM 3M (10 FT)- ADJUSTABLE |
| No specific | AR | CAP - BLANKING |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 131MW, 825 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-42-00-861-001-A | Energize the Ground Service Network from the External Power |
| TASK 52-30-00-860-001-A | Open the FWD or Aft Cargo-Compartment Door with the Yellow Electric Pump |
Subtask 21-43-14-861-050-A ** ON A/C NOT FOR ALL Subtask 21-43-14-865-051-A ** ON A/C NOT FOR ALL
B. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-43-14-010-050-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/FWD CARGO/VENT/CTL & MONG | 2HN | C08 |
C. Get Access
(1) Put the ACCESS PLATFORM 3M (10 FT)- ADJUSTABLE in position at the FWD cargo door 825.
(2) Open the FWD cargo access door 825 (Ref. AMM TASK 52-30-00-860-001).
(3) Remove the access panel 131MW.
4. Procedure(1) Put the ACCESS PLATFORM 3M (10 FT)- ADJUSTABLE in position at the FWD cargo door 825.
(2) Open the FWD cargo access door 825 (Ref. AMM TASK 52-30-00-860-001).
(3) Remove the access panel 131MW.
Subtask 21-43-14-020-050-A ** ON A/C NOT FOR ALL
A. Removal of the Duct Temperature Sensor
(1) Disconnect the electrical connector (1) from the duct temperature sensor (2).
(2) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
(3) Remove the duct temperature sensor (2) from the inlet duct (4).
(4) Remove the O-ring (3).
(1) Disconnect the electrical connector (1) from the duct temperature sensor (2).
(2) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
(3) Remove the duct temperature sensor (2) from the inlet duct (4).
(4) Remove the O-ring (3).
Duct Temperature Sensor (Inlet Duct)