Reactivation of the AFT Cargo Compartment-Heating Trim-Air Valve
TASK 21-43-00-440-002-A
Reactivation of the AFT Cargo Compartment-Heating Trim-Air Valve
MMEL 21-43-02B
AFT CARGO COMPARTMENT HEATING
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 21-43-00-861-055-A ** ON A/C NOT FOR ALL Subtask 21-43-00-865-056-A ** ON A/C NOT FOR ALL
Subtask 21-43-00-440-051-C ** ON A/C NOT FOR ALL
Subtask 21-43-00-410-057-A ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.04.02 06:11:18 UTC
Reactivation of the AFT Cargo Compartment-Heating Trim-Air Valve
WARNING:
MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
1. Reason for the JobMMEL 21-43-02B
AFT CARGO COMPARTMENT HEATING
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 2M (6 FT) |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 197 | REAR FAIRING |
| 197BB | |
| 197KB |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 53-35-13-000-002-A | Removal of the Quick-Release Access Panels from the Belly Fairing Structure |
Subtask 21-43-00-861-055-A ** ON A/C NOT FOR ALL Subtask 21-43-00-865-056-A ** ON A/C NOT FOR ALL
B. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-43-00-941-058-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/AFT CARGO/VENT/CTL & MONG | 31HN | C07 |
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/AFT CARGO/VENT & HTG/CTL & MONG | 31HN | C07 |
C. Safety Precautions
(1) On the panel 30VU:
(a) Make sure that:
(2) On the HP ground connector put a warning notice in position to tell persons not to supply the ground air.
Subtask 21-43-00-010-058-A ** ON A/C NOT FOR ALL (1) On the panel 30VU:
(a) Make sure that:
- the APU BLEED pushbutton switch is in the off position (the ON legend is off) and,
- the ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF legends are on).
(2) On the HP ground connector put a warning notice in position to tell persons not to supply the ground air.
D. Get Access
(1) Put the ACCESS PLATFORM 2M (6 FT) in position at the access panel 197BB.
(2) Remove the access panel 197BB (Ref. AMM TASK 53-35-13-000-002).
Subtask 21-43-00-010-058-C ** ON A/C NOT FOR ALL (1) Put the ACCESS PLATFORM 2M (6 FT) in position at the access panel 197BB.
(2) Remove the access panel 197BB (Ref. AMM TASK 53-35-13-000-002).
D. Get Access
(1) Put the ACCESS PLATFORM 2M (6 FT) in position at the access panel 197KB.
(2) Remove the access panel 197KB (Ref. AMM TASK 53-35-13-000-002).
4. Procedure(1) Put the ACCESS PLATFORM 2M (6 FT) in position at the access panel 197KB.
(2) Remove the access panel 197KB (Ref. AMM TASK 53-35-13-000-002).
Subtask 21-43-00-440-051-C ** ON A/C NOT FOR ALL
A. Reactivation of the Trim Air Valve
(2) Install the quick-release pin (4) in the stowage hole in the body of the trim air valve.
(3) Turn the manual override lever (2) to open the trim air valve.
(4) Remove the temporary attachment and the blanking caps from the electrical connectors (1) and reconnect them.
5. Close-upWARNING:
DO NOT TOUCH THE COMPONENT UNTIL IT IS SUFFICIENTLY
COOL TO PREVENT BURNS.
(1) Remove the quick-release pin (4) from the manual override lever (2). (2) Install the quick-release pin (4) in the stowage hole in the body of the trim air valve.
(3) Turn the manual override lever (2) to open the trim air valve.
(4) Remove the temporary attachment and the blanking caps from the electrical connectors (1) and reconnect them.
Subtask 21-43-00-410-057-A ** ON A/C NOT FOR ALL
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel 197BB.
(3) Remove the access platform(s).
(4) Remove the WARNING NOTICE(S).
Subtask 21-43-00-410-057-C ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel 197BB.
(3) Remove the access platform(s).
(4) Remove the WARNING NOTICE(S).
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel 197KB.
(3) Remove the access platform(s).
(4) Remove the WARNING NOTICE(S).
Subtask 21-43-00-862-061-A ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel 197KB.
(3) Remove the access platform(s).
(4) Remove the WARNING NOTICE(S).