Detailed Inspection of Demister Drain Hose Connection Area
TASK 21-26-42-210-001-A
Detailed Inspection of Demister Drain Hose Connection Area
Refer to the MPD TASK: 212600-06
DETAILED INSPECTION OF DEMISTER DRAIN HOSE CONNECTION AREA
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 21-26-42-861-054-A ** ON A/C NOT FOR ALL Subtask 21-26-42-941-055-A ** ON A/C NOT FOR ALL
Subtask 21-26-42-020-054-D ** ON A/C NOT FOR ALL
Subtask 21-26-42-410-053-A ** ON A/C NOT FOR ALL
[Rev.10 from 2021]
2026.04.02 06:11:05 UTC
Detailed Inspection of Demister Drain Hose Connection Area
WARNING:
PUT ON GLOVES, A COVERALL WITH A HOOD, GOGGLES AND A PARTICULATE RESPIRATOR BEFORE YOU TOUCH THE FILTER. THE FILTER REMOVES SMALL PARTICLES (SMOKE, DUST, LINT, FIBERS, POLLEN) AND INFECTIOUS MATERIALS (BACTERIA, VIRUSES, MOLD SPORES, FUNGI) FROM THE AIR. THESE MATERIALS CAN CAUSE ILLNESS.
WARNING:
DO NOT LET THE FILTER TOUCH YOUR SKIN. DO NOT SHAKE OR HIT THE FILTER. DO NOT LET THE FILTER FALL. DO NOT USE COMPRESSED AIR TO CLEAN THE FILTER OR FILTER HOUSING. THIS CAN CAUSE THE INFECTIOUS MATERIAL TO BECOME AIRBORNE. DISCARD THE FILTER IN A PLASTIC DISPOSAL BAG. IF YOU DO NOT OBEY THESE INSTRUCTIONS, INFECTIOUS MATERIAL FROM THE FILTER CAN CAUSE ILLNESS.
WARNING:
PUT ALL AIR FILTERS THAT YOU REMOVE FROM THE AIRCRAFT INTO PLASTIC DISPOSAL BAGS. AIR FILTERS CAN CONTAIN INFECTIOUS MATERIALS WHICH CAN CAUSE ILLNESS. OBEY AIRLINE POLICY AND LOCAL HEALTH DEPARTMENT AND LAW ENFORCEMENT REGULATIONS FOR DISPOSAL OF INFECTIOUS MATERIALS.
CAUTION:
USE ONLY THE GROUND SERVICE NETWORK TO SUPPLY ELECTRICITY BECAUSE THE AVIONICS VENTILATION SYSTEM IS NOT SERVICEABLE. IF YOU ENERGIZE THE AIRCRAFT ELECTRICAL CIRCUITS WITHOUT THE VENTILATION SYSTEM YOU WILL CAUSE DAMAGE TO ELECTRICAL EQUIPMENT.
ZONE: 120
1. Reason for the JobRefer to the MPD TASK: 212600-06
DETAILED INSPECTION OF DEMISTER DRAIN HOSE CONNECTION AREA
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | AR | ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| No specific | AR | WARNING NOTICE(S) |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 120 | AVIONICS COMPARTMENT |
| 824 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-42-00-861-001-A | Energize the Ground Service Network from the External Power |
| TASK 24-42-00-862-001-A | De-energize the Ground Service Network Supplied from the External Power |
| TASK 52-41-00-410-002-A | Close the Avionics Compartment Doors after Access |
Subtask 21-26-42-861-054-A ** ON A/C NOT FOR ALL Subtask 21-26-42-941-055-A ** ON A/C NOT FOR ALL
B. Safety Precautions
(1) On the AIR COND panel 30VU:
(a) Make sure that the APU BLEED, all ENG BLEED and all PACK pushbutton switches are released (the OFF legends are on).
(b) Put a WARNING NOTICE(S) in position to tell persons not to operate these pushbutton switches.
(2) On the HP and LP ground connectors, put a warning notice in position to tell persons not to supply the ground air sources.
Subtask 21-26-42-865-057-A ** ON A/C NOT FOR ALL (1) On the AIR COND panel 30VU:
(a) Make sure that the APU BLEED, all ENG BLEED and all PACK pushbutton switches are released (the OFF legends are on).
(b) Put a WARNING NOTICE(S) in position to tell persons not to operate these pushbutton switches.
(2) On the HP and LP ground connectors, put a warning notice in position to tell persons not to supply the ground air sources.
C. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-26-42-010-054-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/AVNCS VENT/CTL | 6HQ | D06 |
| 49VU | AIR COND/AVNCS VENT/CTL | 5HQ | D05 |
| 122VU | AIR COND/AVNCS/VENT/MONG | 3HQ | Y17 |
| 123VU | AVNCS VENT/EXTC/FAN | 2HQ | AC04 |
| 123VU | AVNCS VENT/BLOWER/FAN | 1HQ | AD10 |
D. Get Access
(1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
4. Procedure(1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
Subtask 21-26-42-020-054-D ** ON A/C NOT FOR ALL
A. Removal of the Demister Filter
(1) Turn the seven door fasteners of the filter housing (1) and open the door.
(2) Remove the demister filter (6).
Subtask 21-26-42-210-056-D ** ON A/C NOT FOR ALL (1) Turn the seven door fasteners of the filter housing (1) and open the door.
(2) Remove the demister filter (6).
B. Visual Inspection of the Filter Assembly
(1) Do a visual inspection of the filter assembly for signs of impact, distortion and defective welding.
(2) Make sure that the syphon assembly (2) is in the correct condition.
(3) If not, replace it:
(a) Remove the four screws (3) and the four washers (4) from the syphon assembly (2).
(b) Release the upper clamp (5) from the hose of the syphon assembly (2).
(c) Remove the syphon assembly (2) from the filter housing (1).
(d) Put a new syphon assembly (2) in position below the filter housing (1).
(e) Connect the hose of the syphon assembly (2) to the filter housing (1) and safety it with the upper clamp (5).
(f) Install the four washers (4) and the four screws (3) on the syphon assembly (2) and tighten.
Subtask 21-26-42-420-054-D ** ON A/C NOT FOR ALL (1) Do a visual inspection of the filter assembly for signs of impact, distortion and defective welding.
(2) Make sure that the syphon assembly (2) is in the correct condition.
(3) If not, replace it:
(a) Remove the four screws (3) and the four washers (4) from the syphon assembly (2).
(b) Release the upper clamp (5) from the hose of the syphon assembly (2).
(c) Remove the syphon assembly (2) from the filter housing (1).
(d) Put a new syphon assembly (2) in position below the filter housing (1).
(e) Connect the hose of the syphon assembly (2) to the filter housing (1) and safety it with the upper clamp (5).
(f) Install the four washers (4) and the four screws (3) on the syphon assembly (2) and tighten.
C. Installation of the Demister Filter
(1) Put the demister filter (6) in position in the filter housing (1).
(2) Turn and safety the seven door fasteners of the filter housing (1) to close the door.
5. Close-up(1) Put the demister filter (6) in position in the filter housing (1).
(2) Turn and safety the seven door fasteners of the filter housing (1) to close the door.
Subtask 21-26-42-410-053-A ** ON A/C NOT FOR ALL
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
Subtask 21-26-42-865-058-A ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-26-42-862-054-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/AVNCS VENT/CTL | 6HQ | D06 |
| 49VU | AIR COND/AVNCS VENT/CTL | 5HQ | D05 |
| 122VU | AIR COND/AVNCS/VENT/MONG | 3HQ | Y17 |
| 123VU | AVNCS VENT/EXTC/FAN | 2HQ | AC04 |
| 123VU | AVNCS VENT/BLOWER/FAN | 1HQ | AD10 |
Filter Assembly (Siphon and Drain Hose) and Ventilation Duct (Drain Hose)