Installation of the Avionics-Ventilation Blower and Extract Fan Pressure-Switches


TASK 21-26-11-400-001-A
Installation of the Avionics-Ventilation Blower and Extract Fan Pressure-Switches


ZONE: 121
ZONE: 125
ZONE: 127
ZONE: 128
FIN: 17HQ
FIN: 19HQ
FIN: 30HQ
1. Reason for the Job
Self explanatory
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
AR
ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE
No specific
Torque wrench: range to between 2.5 and 2.1 m.N (22.12 and 18.58 lbf.in ) T
No specific
Torque wrench: range to between 4.0 and 3.6 m.N (35.40 and 31.86 lbf.in ) T
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
121
AVIONICS COMPARTMENT
125
LATERAL AVIONIC COMPARTMENT
127
REAR AVIONIC COMPARTMENT
128
REAR AVIONIC COMPARTMENT
811, 824
FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
811
FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
824
FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
824
 C. Expendable Parts
FIG.ITEM
DESIGNATION
IPC-CSN
5
ORING
AIPC 21-26-01-04-080
2
ORING
AIPC 21-26-01-16-035
5
ORING
AIPC 21-26-81-04-060
2
ORING
AIPC 21-26-81-16-050
 D. Referenced Information
REFERENCE
DESIGNATION
TASK 21-26-00-710-001-A
Operational Check of the Avionics Equipment Ventilation-System via MCDU
TASK 21-26-00-710-001-A-01
Operational Check of the Avionics Equipment Ventilation (without the CFDS)
TASK 21-26-11-710-001-A
Operational Test of the Extract-Fan Pressure Switch (without the CFDS)
TASK 24-42-00-861-001-A
Energize the Ground Service Network from the External Power
TASK 24-42-00-862-001-A
De-energize the Ground Service Network Supplied from the External Power
FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
TASK 52-41-00-410-002-A
Close the Avionics Compartment Doors after Access
FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
TASK 52-41-00-410-002-A
Close the Avionics Compartment Doors after Access
FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
TASK 52-41-00-410-002-A
Close the Avionics Compartment Doors after Access
3. Job Set-up
Subtask 21-26-11-860-052-A
A. Aircraft Maintenance Configuration
   (1) Make sure that the ground service network is energized (Ref. AMM TASK 24-42-00-861-001).
Subtask 21-26-11-010-051-A
B. Get Access
   (1) Make sure that the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE is in position at access doors 811 and 824.
   (2) Make sure that the access doors that follow are open:
     (a) FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
811 (Ref. AMM TASK 52-41-00-010-002).
     (b) FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
824 (Ref. AMM TASK 52-41-00-010-002).
     (c) FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
824 (Ref. AMM TASK 52-41-00-010-002).
Subtask 21-26-11-865-051-A
C. Make sure that this(these) circuit breaker(s) is(are) open, safetied and tagged:
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
FOR FIN: 19HQ (PRESS SWBLOWER FAN, AVNCS VENT) FOR FIN: 17HQ (PRESS SWBLOWER FAN, AVNCS VENT)
49VUAIR COND/AVNCS VENT/CTL6HQD06
49VUAIR COND/AVNCS VENT/CTL5HQD05
122VUAIR COND/AVNCS/VENT/MONG3HQY17
123VUAVNCS VENT/BLOWER/FAN1HQAD10
FOR FIN: 30HQ (PRESS SWEXTRACT FAN, AVNCS VENT)
49VUAIR COND/AVNCS VENT/CTL6HQD06
49VUAIR COND/AVNCS VENT/CTL5HQD05
** ON A/C NOT FOR ALL
123VUAVNCS VENT/EXTC/FAN2HQAE02
** ON A/C NOT FOR ALL
123VUAVNCS VENT/EXTC/FAN2HQAC04
4. Procedure
CAUTION: MAKE SURE THAT THE PIPE POSITION AT THE PRESSURE SWITCHES IS CORRECT. FOR PRESSURE SWITCHES 17HQ AND 19HQ, THE PIPE MUST BE CONNECTED TO THE CENTER OF THE PRESSURE SWITCH. FOR PRESSURE SWITCH 30HQ, THE PIPE MUST BE CONNECTED TO THE PERIPHERAL PORT. IF THE POSITION OF THE PIPE IS NOT CORRECT, FAILURE CAN OCCUR.
Subtask 21-26-11-420-050-A
A. Installation of the Avionics-Ventilation Blower-Fan Pressure-Switch
   (1) When you connect/install the components, refer to the match marks made during the removal procedure.
   (2) Clean the component interfaces and the adjacent area.
   (3) Do a visual inspection of the component interfaces and the adjacent area.
   (4) Make sure that the parts retained from the removed component are clean and in the correct condition.
   (5) Remove the PLUG-BLANKING from each disconnected line end.
   (6) Install the new AIPC 21-26-01-04-080 ORING (5) or AIPC 21-26-81-04-060 ORING (5) in position on the reducer (6).
   (7) Install the reducer on the avionics-ventilation blower-fan pressure-switch (2).
   (8) TORQUE the reducer (6) to between 4.0 and 3.6 m.N (35.40 and 31.86 lbf.in )
T.
   (9) Install the blanking cap (8) on the reducer (6).
   (10) TORQUE the blanking cap (8) to between 4.0 and 3.6 m.N (35.40 and 31.86 lbf.in )
T.
   (11) Install the avionics-ventilation blower-fan pressure-switch (2) in position on its support and hold it in position.
   (12) Install the washers (3) and the screws (4).
   (13) Tighten the screws (4).
   (14) Connect the pipe (7).
   (15) TORQUE the pipe (7) to between 2.5 and 2.1 m.N (22.12 and 18.58 lbf.in )
T.
   (16) Connect the electrical connector (1) as follows:
     (a) Remove the CAP-BLANKING from each electrical connector and receptacle.
CAUTION: MAKE SURE THAT THE ELECTRICAL CONNECTORS ARE CLEAN BEFORE YOU DISCONNECT OR CONNECT THEM. CONTAMINATION ON THE ELECTRICAL CONNECTORS CAN CAUSE DAMAGE TO EQUIPMENT.
     (b) Connect the electrical connector (1) to the avionics-ventilation blower-fan pressure-switch (2).
Subtask 21-26-11-420-051-A
B. Installation of the Avionics-Ventilation Extract-Fan Pressure-Switch
   (1) When you connect/install the components, refer to the match marks made during the removal procedure.
   (2) Clean the component interfaces and the adjacent area.
   (3) Do a visual inspection of the component interfaces and the adjacent area.
   (4) Make sure that the parts retained from the removed component are clean and in the correct condition.
   (5) Remove the PLUG-BLANKING from each disconnected line end.
   (6) Install the new
AIPC 21-26-01-16-035 ORING (2) or AIPC 21-26-81-16-050 ORING (2) in position on the reducer (3).
   (7) Install the reducer (3).
   (8) TORQUE the reducer (3) to between 4.0 and 3.6 m.N (35.40 and 31.86 lbf.in )
T.
   (9) Install the blanking cap (5) on the avionics-ventilation extract-fan pressure-switch (8).
   (10) TORQUE the blanking cap (5) to between 2.5 and 2.1 m.N (22.12 and 18.58 lbf.in )
T.
   (11) Install the avionics-ventilation extract-fan pressure-switch (8) in position on its support (1) and hold it in position.
   (12) Install the washers (7) and the screws (6).
   (13) Tighten the screws (6).
   (14) Connect the pipe (4) to the reducer (3).
   (15) TORQUE the pipe (4) to between 4.0 and 3.6 m.N (35.40 and 31.86 lbf.in )
T.
   (16) Connect the electrical connector (9) as follows:
     (a) Remove the CAP-BLANKING from each electrical connector and receptacle.
CAUTION: MAKE SURE THAT THE ELECTRICAL CONNECTORS ARE CLEAN BEFORE YOU DISCONNECT OR CONNECT THEM. CONTAMINATION ON THE ELECTRICAL CONNECTORS CAN CAUSE DAMAGE TO EQUIPMENT.
     (b) Connect the electrical connector (9) to the avionics-ventilation extract-fan pressure-switch (8).
Subtask 21-26-11-865-052-A
C. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
FOR FIN: 19HQ (PRESS SWBLOWER FAN, AVNCS VENT) FOR FIN: 17HQ (PRESS SWBLOWER FAN, AVNCS VENT)
49VUAIR COND/AVNCS VENT/CTL6HQD06
49VUAIR COND/AVNCS VENT/CTL5HQD05
122VUAIR COND/AVNCS/VENT/MONG3HQY17
123VUAVNCS VENT/BLOWER/FAN1HQAD10
FOR FIN: 30HQ (PRESS SWEXTRACT FAN, AVNCS VENT)
49VUAIR COND/AVNCS VENT/CTL6HQD06
49VUAIR COND/AVNCS VENT/CTL5HQD05
** ON A/C NOT FOR ALL
123VUAVNCS VENT/EXTC/FAN2HQAE02
** ON A/C NOT FOR ALL
123VUAVNCS VENT/EXTC/FAN2HQAC04
Subtask 21-26-11-710-050-A
D. Do an operational test of the ventilation system of the avionics equipment (Ref. AMM TASK 21-26-00-710-001).
NOTE: As an alternative procedure , you can do this operational test without the CFDS for the extract fan pressure switch (30HQ) only (Ref. AMM TASK 21-26-11-710-001) (the CFDS is necessary for the operational test of the blower fan pressures switches 17HQ and 19HQ).
5. Close-up
Subtask 21-26-11-410-050-A
A. Close Access
   (1) Make sure that the work area is clean and clear of tools and other items.
   (2) Close the access doors that follow:
     (a) FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
     (b) FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
     (c) FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
   (3) Remove the access platform(s).
Subtask 21-26-11-862-051-A
B. De-energize the ground service network (Ref. AMM TASK 24-42-00-862-001).