Removal of the Avionics-Ventilation Blower and Extract Fan Pressure-Switches


TASK 21-26-11-000-001-A
Removal of the Avionics-Ventilation Blower and Extract Fan Pressure-Switches


ZONE: 121
ZONE: 125
ZONE: 127
ZONE: 128
FIN: 17HQ
FIN: 19HQ
FIN: 30HQ
1. Reason for the Job
Self explanatory
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
1
ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE
No specific
AR
CAP - BLANKING
No specific
AR
PLUG - BLANKING
No specific
AR
SAFETY CLIP - CIRCUIT BREAKER
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
121
AVIONICS COMPARTMENT
125
LATERAL AVIONIC COMPARTMENT
127
REAR AVIONIC COMPARTMENT
128
REAR AVIONIC COMPARTMENT
811, 824
FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
811
FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
824
FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
824
 C. Referenced Information
REFERENCE
DESIGNATION
TASK 24-42-00-861-001-A
Energize the Ground Service Network from the External Power
FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
3. Job Set-up
Subtask 21-26-11-861-050-A
A. Energize the ground service network (Ref. AMM TASK 24-42-00-861-001).
Subtask 21-26-11-010-050-A
B. Get Access
   (1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at access doors 811 and 824.
   (2) Open the access doors that follow:
     (a) FOR [17HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
     (b) FOR [19HQ] (PRESS SW-BLOWER FAN, AVNCS VENT)
     (c) FOR [30HQ] (PRESS SW-EXTRACT FAN, AVNCS VENT)
Subtask 21-26-11-865-050-A
C. Open, safety and tag this(these) circuit breaker(s):
PANELDESIGNATIONFINLOCATION
** ON A/C ALL
FOR FIN: 19HQ (PRESS SWBLOWER FAN, AVNCS VENT) FOR FIN: 17HQ (PRESS SWBLOWER FAN, AVNCS VENT)
49VUAIR COND/AVNCS VENT/CTL6HQD06
49VUAIR COND/AVNCS VENT/CTL5HQD05
122VUAIR COND/AVNCS/VENT/MONG3HQY17
123VUAVNCS VENT/BLOWER/FAN1HQAD10
FOR FIN: 30HQ (PRESS SWEXTRACT FAN, AVNCS VENT)
49VUAIR COND/AVNCS VENT/CTL6HQD06
49VUAIR COND/AVNCS VENT/CTL5HQD05
** ON A/C NOT FOR ALL
123VUAVNCS VENT/EXTC/FAN2HQAE02
** ON A/C NOT FOR ALL
123VUAVNCS VENT/EXTC/FAN2HQAC04
4. Procedure
Subtask 21-26-11-020-052-A
A. Removal of the Avionics-Ventilation Extract-Fan Pressure-Switch
   (1) Make match marks on the components that you disconnect/remove to record their connections/positions. This is important for the subsequent installation procedure.
CAUTION: MAKE SURE THAT THE ELECTRICAL CONNECTORS ARE CLEAN BEFORE YOU DISCONNECT OR CONNECT THEM. CONTAMINATION ON THE ELECTRICAL CONNECTORS CAN CAUSE DAMAGE TO EQUIPMENT.
   (2) Disconnect the electrical connector (9) as follows:
     (a) Disconnect the electrical connector (9) from the avionics-ventilation extract-fan pressure-switch (8).
     (b) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
   (3) Disconnect the pipe (4) from the reducer (3).
   (4) Remove the reducer (3) from the avionics-ventilation extract-fan pressure-switch (8).
   (5) Remove the blanking cap (5) from the avionics-ventilation extract-fan pressure-switch (8).
   (6) Put the PLUG-BLANKING in each disconnected line end.
   (7) Hold the avionics-ventilation extract-fan pressure-switch (8) and remove the screws (6) and the washers (7).
   (8) Remove the avionics-ventilation extract-fan pressure-switch (8) from its support (1).
   (9) Remove the O-ring (2) and discard it.
Subtask 21-26-11-020-051-A
B. Removal of the Avionics-Ventilation Blower-Fan Pressure-Switch
   (1) Make match marks on the components that you disconnect/remove to record their connections/positions. This is important for the subsequent installation procedure.
CAUTION: MAKE SURE THAT THE ELECTRICAL CONNECTORS ARE CLEAN BEFORE YOU DISCONNECT OR CONNECT THEM. CONTAMINATION ON THE ELECTRICAL CONNECTORS CAN CAUSE DAMAGE TO EQUIPMENT.
   (2) Disconnect the electrical connector (1) as follows:
     (a) Disconnect the electrical connector (1) from the avionics-ventilation blower-fan pressure-switch (2).
     (b) Put the CAP-BLANKING on each disconnected electrical connector and receptacle.
   (3) Disconnect the pipe (7).
   (4) Remove the blanking cap (8) from the reducer (6).
   (5) Remove the reducer (6) from the avionics-ventilation blower-fan pressure-switch (2).
   (6) Put the PLUG-BLANKING in each disconnected line end.
   (7) Hold the avionics-ventilation blower-fan pressure-switch (2) and remove the screws (4) and the washers (3).
   (8) Remove the avionics-ventilation blower-fan pressure-switch (2) from its support.
   (9) Remove the O-ring (5) and discard it.