Operational Check of Fan High Speed Mode
TASK 21-26-00-710-013-A
Operational Check of Fan High Speed Mode
1. Reason for the Job
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 21-26-00-861-072-A ** ON A/C NOT FOR ALL
Subtask 21-26-00-480-051-A ** ON A/C NOT FOR ALL
Subtask 21-26-00-720-053-A ** ON A/C NOT FOR ALL
Subtask 21-26-00-865-092-A ** ON A/C NOT FOR ALL
[Rev.9 from 2019]
2026.04.02 06:11:01 UTC
Operational Check of Fan High Speed Mode
1. Reason for the Job
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | AR | ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE |
| No specific | AR | CAP - BLANKING |
| No specific | AR | SAFETY CLIP - CIRCUIT BREAKER |
| 97D21503000000 | 1 | TEST TOOL-TWO SPEED FANS |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 128 | REAR AVIONIC COMPARTMENT |
| 210 | CKPT,FWD COMPT BHD TO FLT COMPT BULKHEAD |
| 824 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 52-41-00-410-002-A | Close the Avionics Compartment Doors after Access |
Subtask 21-26-00-861-072-A ** ON A/C NOT FOR ALL
A. Energize the aircraft electrical circuits
(Ref. AMM TASK 24-41-00-861-002).
Subtask 21-26-00-865-091-A ** ON A/C NOT FOR ALL (Ref. AMM TASK 24-41-00-861-002).
NOTE: The energization of the aircraft electrical circuits starts a full test of the ventilation system. The test continues for 2 minutes approximately.
B. Open, safety and tag this(these) circuit breaker(s):
Subtask 21-26-00-010-085-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/AVNCS VENT/CTL | 6HQ | D06 |
| 49VU | AIR COND/AVNCS VENT/CTL | 5HQ | D05 |
| 122VU | AIR COND/AVNCS/VENT/MONG | 3HQ | Y17 |
| 123VU | AVNCS VENT/BLOWER/FAN | 1HQ | AD10 |
| 123VU | AVNCS VENT/EXTC/FAN | 2HQ | AE02 |
C. Get Access
(1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
4. Procedure(1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
(2) Open the access door 824.
Subtask 21-26-00-480-051-A ** ON A/C NOT FOR ALL
A. Installation of the Testing Tool
(1) Disconnect the electrical connector (1) from the sensor (2).
(2) Connect the connector (3) of the 97D21503000000 TEST TOOL-TWO SPEED FANS (4) to the sensor (2).
(3) Connect the electrical connector (1) to the connector (6) of the 97D21503000000 TEST TOOL-TWO SPEED FANS (4).
Subtask 21-26-00-720-052-A ** ON A/C NOT FOR ALL (1) Disconnect the electrical connector (1) from the sensor (2).
(2) Connect the connector (3) of the 97D21503000000 TEST TOOL-TWO SPEED FANS (4) to the sensor (2).
(3) Connect the electrical connector (1) to the connector (6) of the 97D21503000000 TEST TOOL-TWO SPEED FANS (4).
CAUTION:
IF THE TEMPERATURE OF THE BLOWN AIR (SENSED BY SENSOR 32HQ) IS HIGHER OR EQUAL TO 35°C, DO NOT DO THIS TEST FOR MORE THAN 5 MIN. IF THE TEST CONTINUES FOR MORE THAN 5 MIN, THERE IS A RISK OF DAMAGE TO THE EQUIPMENT IN THE AVIONICS COMPARTMENT (NOT SUFFICIENT VENTILATION).
B. Functional Test of the Low Speed | ACTION | RESULT |
|---|---|
| 1.On the 97D21503000000 TEST TOOL-TWO SPEED FANS (4), make sure that the switch (5) is in the AUTO position. | |
| 2.Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s): 1HQ, 2HQ, 3HQ, 5HQ, 6HQ. NOTE: The energization of the aircraft electrical circuits starts a full test of the ventilation system. The test continues for 2 minutes approximately. | |
| 3.On the 97D21503000000 TEST TOOL-TWO SPEED FANS (4), set the switch (5) to the LOW SPEED position. |
|
| 4.Set the switch (5) to the AUTO position. |
C. Functional Test of the High Speed
5. Close-up| ACTION | RESULT |
|---|---|
| 1.On the 97D21503000000 TEST TOOL-TWO SPEED FANS (4), set the switch (5) to the HIGH SPEED position. |
|
| 2.Set the switch (5) to the AUTO position. | |
| 3.Open, safety and tag this(these) circuit breaker(s): 1HQ, 2HQ, 3HQ, 5HQ, 6HQ. | |
| 4.Disconnect the electrical connector (1) from the connector (6) of the 97D21503000000 TEST TOOL-TWO SPEED FANS (4). | |
| 5.Disconnect the connector (3) of the 97D21503000000 TEST TOOL-TWO SPEED FANS (4) from the sensor (2). | |
| 6.Connect the electrical connector (1) to the sensor (2). | |
| 7.Put CAP - BLANKING on the disconnected connectors. |
Subtask 21-26-00-865-092-A ** ON A/C NOT FOR ALL
A. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-26-00-860-070-A ** ON A/C NOT FOR ALL | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C NOT FOR ALL | |||
| 49VU | AIR COND/AVNCS VENT/CTL | 6HQ | D06 |
| 49VU | AIR COND/AVNCS VENT/CTL | 5HQ | D05 |
| 122VU | AIR COND/AVNCS/VENT/MONG | 3HQ | Y17 |
| 123VU | AVNCS VENT/BLOWER/FAN | 1HQ | AD10 |
| 123VU | AVNCS VENT/EXTC/FAN | 2HQ | AE02 |
B. Condition of the Automatic Start of the Ventilation System Test.
Subtask 21-26-00-410-082-A ** ON A/C NOT FOR ALL NOTE: The energization of the aircraft electrical circuits starts a full test of the ventilation system. The test continues for 2 minutes approximately.
NOTE: If the temperature sensed by the sensor 32HQ is more than 40 degrees celsius ( 194 degrees fahrenheit ), the two fans operate at high speed.
If the temperature sensed by the sensor 32HQ is less than 35 degrees celsius ( 95 degrees fahrenheit), the two fans operate at low speed.
If the temperature sensed by the sensor 32HQ is less than 35 degrees celsius ( 95 degrees fahrenheit), the two fans operate at low speed.
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
Subtask 21-26-00-862-072-A ** ON A/C NOT FOR ALL (1) Make sure that the work area is clean and clear of tools and other items.
(2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
(3) Remove the access platform(s).
Testing Tool Installation