Extract Fan Inoperative - Check of Conditioned-Air Inlet Valve Open


TASK 21-26-00-040-007-A
Extract Fan Inoperative - Check of Conditioned-Air Inlet Valve Open


Task Summary
Access Test Specific Tools Mhr E/T Nb Men
YESYESNO0.50.51
1. Reason for the Job
MMEL 21-26-02B
AVIONICS EXTRACT FAN
2. Job Set-up Information
 A. Fixtures, Tools, Test and Support Equipment
REFERENCE
QTY
DESIGNATION
No specific
AR
ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE
No specific
AR
WARNING NOTICE(S)
 B. Work Zones and Access Panels
ZONE/ACCESS
ZONE DESCRIPTION
824
 C. Referenced Information
REFERENCE
DESIGNATION
TASK 24-41-00-861-002-A
Energize the Aircraft Electrical Circuits from the External Power
TASK 24-41-00-861-002-A-01
Energize the Aircraft Electrical Circuits from the APU
TASK 24-41-00-861-002-A-02
Energize the Aircraft Electrical Circuits from Engine 1(2)
TASK 24-41-00-862-002-A
De-energize the Aircraft Electrical Circuits Supplied from the External Power
TASK 24-41-00-862-002-A-01
De-energize the Aircraft Electrical Circuits Supplied from the APU
TASK 24-41-00-862-002-A-02
De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2)
TASK 31-60-00-860-001-A
EIS Start Procedure
TASK 31-60-00-860-002-A
EIS Stop Procedure
TASK 52-41-00-010-002-A
Open the Avionics Compartment Doors for Access
TASK 52-41-00-410-002-A
Close the Avionics Compartment Doors after Access
3. Job Set-up
Subtask 21-26-00-861-075-A
A. Aircraft Maintenance Configuration
   (1) Energize the aircraft electrical circuits
(Ref. AMM TASK 24-41-00-861-002).
   (2) Do the EIS start procedure (upper ECAM DU and lower ECAM DU only)
(Ref. AMM TASK 31-60-00-860-001).
Subtask 21-26-00-010-065-A
B. Get Access
   (1) Put the ACCESS PLATFORM 2M (6 FT) - ADJUSTABLE in position at the access door 824.
   (2) Open the access door 824 (Ref. AMM TASK 52-41-00-010-002).
4. Procedure
Subtask 21-26-00-040-056-A
A. Conditioned Air Inlet Valve
   (1) Make sure that the operation of avionics equipment ventilation with electrical ground power, has the time limits that follow:
  • outside air temperature 38 deg.C or less, no time limit
  • outside air temperature 45 deg.C, maximum of 3 hours
  • outside air temperature 55 deg.C, maximum of thirty five minutes.
   (2) On the VENTILATION section of the overhead control and indicating panel 22VU:
  • Release the EXTRACT pushbutton switch (the OVRD legend comes on).
   (3) On the bottom part of the upper ECAM display unit:
  • the VENT EXTRACT FAULT warning comes into view.
Disregard this warning.
On the ECAM control panel:
  • push the CLR key.
   (4) If the VENT BLOWER FAULT warning comes into view:
  • push the CAB FANS pushbutton switch on the VENTILATION section of the panel 22VU (the OFF legend goes off),
  • make sure that the VENT BLOWER FAULT warning goes out of view.
   (5) In the avionics compartment:
  • Make sure that the conditioned-air inlet valve 21HQ is open (the position indicator of the valve is at 0).
5. Close-up
Subtask 21-26-00-410-066-A
A. Close Access
   (1) Make sure that the work area is clean and clear of tools and other items.
   (2) Close the access door 824 (Ref. AMM TASK 52-41-00-410-002).
   (3) Remove the access platform(s).
Subtask 21-26-00-942-079-A
B. Safety Precautions
   (1) Put a WARNING NOTICE(S) in the cockpit to tell the crew that the Extract Fan is deactivated.
   (2) Make an entry in the logbook.
Subtask 21-26-00-862-081-A
C. Aircraft Maintenance Configuration
   (1) Do the EIS stop procedure
(Ref. AMM TASK 31-60-00-860-002).
   (2) De-energize the aircraft electrical circuits
(Ref. AMM TASK 24-41-00-862-002).