Installation of the Recirculation Check Valve
TASK 21-21-42-400-001-A
Installation of the Recirculation Check Valve
Self explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
B. Work Zones and Access Panels
C. Referenced Information
3. Job Set-up
Subtask 21-21-42-860-050-A
Subtask 21-21-42-420-050-A
Subtask 21-21-42-410-050-A
[Rev.10 from 2021]
2026.04.02 06:10:54 UTC
Installation of the Recirculation Check Valve
WARNING:
MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.
NOTE: The procedure is the same for the recirculation check valves 4020HM (4021HM).
1. Reason for the JobSelf explanatory
2. Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment
| REFERENCE | QTY | DESIGNATION |
|---|---|---|
| No specific | 1 | ACCESS PLATFORM 2M (6 FT) |
| No specific | AR | WARNING NOTICE(S) |
| No specific | Torque wrench: range to between 1.120 and 0.916 m.daN (99.12 and 81.06 lbf.in ) ![]() |
| ZONE/ACCESS | ZONE DESCRIPTION |
|---|---|
| 825 |
| REFERENCE | DESIGNATION |
|---|---|
| TASK 24-41-00-861-002-A | Energize the Aircraft Electrical Circuits from the External Power |
| TASK 24-41-00-861-002-A-01 | Energize the Aircraft Electrical Circuits from the APU |
| TASK 24-41-00-861-002-A-02 | Energize the Aircraft Electrical Circuits from Engine 1(2) |
| TASK 24-41-00-862-002-A | De-energize the Aircraft Electrical Circuits Supplied from the External Power |
| TASK 24-41-00-862-002-A-01 | De-energize the Aircraft Electrical Circuits Supplied from the APU |
| TASK 24-41-00-862-002-A-02 | De-energize the Aircraft Electrical Circuits Supplied from the Engine 1(2) |
| TASK 25-54-12-000-001-A | Removal of the Forward Cargo-Compartment Partition |
| TASK 25-54-12-400-001-A | Installation of the Forward Cargo-Compartment Partition |
| TASK 52-30-00-860-001-A | Open the FWD or Aft Cargo-Compartment Door with the Yellow Electric Pump |
| TASK 52-30-00-860-002-A | Close the FWD or Aft Cargo-Compartment Door with the Yellow Electric Pump |
| FOR [4020HM] (RECIRC CHECK VALVE 1) | |
| TASK 06-41-53-00 | FUSELAGE-DESCRIPTION AND OPERATION |
| FOR [4021HM] (RECIRC CHECK VALVE 2) | |
| TASK 06-41-53-00 | FUSELAGE-DESCRIPTION AND OPERATION |
Subtask 21-21-42-860-050-A
A. Aircraft Maintenance Configuration
(1) Make sure that:
(a) The aircraft electrical circuits are energized (Ref. AMM TASK 24-41-00-861-002).
(b) On panel 30VU:
1 The APU BLEED pushbutton switch is in the off position (the ON legend is off).
2 The ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF legends are on).
3 The WARNING NOTICE(S) is in position to tell persons not to operate the pushbutton switches.
(c) On the ground connector, the WARNING NOTICE(S) is in position to tell persons not to supply ground air.
(d) FWD cargo-compartment door 825 is open (Ref. AMM TASK 52-30-00-860-001).
(e) An ACCESS PLATFORM 2M (6 FT) is in position at FWD cargo-compartment door 825.
(2) Make sure that the access panel(s) are removed from partition FR34 (Ref. AMM TASK 25-54-12-000-001):
(a) FOR [4020HM] (RECIRC CHECK VALVE 1)
(b) FOR [4021HM] (RECIRC CHECK VALVE 2)
Subtask 21-21-42-865-051-A (1) Make sure that:
(a) The aircraft electrical circuits are energized (Ref. AMM TASK 24-41-00-861-002).
(b) On panel 30VU:
1 The APU BLEED pushbutton switch is in the off position (the ON legend is off).
2 The ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF legends are on).
3 The WARNING NOTICE(S) is in position to tell persons not to operate the pushbutton switches.
(c) On the ground connector, the WARNING NOTICE(S) is in position to tell persons not to supply ground air.
(d) FWD cargo-compartment door 825 is open (Ref. AMM TASK 52-30-00-860-001).
(e) An ACCESS PLATFORM 2M (6 FT) is in position at FWD cargo-compartment door 825.
(2) Make sure that the access panel(s) are removed from partition FR34 (Ref. AMM TASK 25-54-12-000-001):
(a) FOR [4020HM] (RECIRC CHECK VALVE 1)
(b) FOR [4021HM] (RECIRC CHECK VALVE 2)
B. Make sure that this(these) circuit breaker(s) is(are) open, safetied and tagged:
4. Procedure| PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| FOR FIN: 4020HM (RECIRC CHECK VALVE 1) | |||
| 122VU | AIR COND/RECIRC FAN/L/CTL | 2HG | X20 |
| 122VU | AIR COND/RECIRC FAN/L/SPLY | 1HG | X18 |
| FOR FIN: 4021HM (RECIRC CHECK VALVE 2) | |||
| 122VU | AIR COND/RECIRC FAN/R/CTL | 11HG | W20 |
| 122VU | AIR COND/RECIRC FAN/R/SPLY | 3HG | W18 |
Subtask 21-21-42-420-050-A
A. Installation of the Recirculation Check Valve
(1) Remove the blanking plugs from the disconnected line ends.
(2) Clean the component interfaces and the adjacent area.
(3) Make sure that the parts retained from the removed component are clean and in the correct condition.
(4) Put the recirculation check valve (2) in position in the flange (3).
(5) Put the flange (3) (together with the recirculation check valve (2)) in position in the sleeve (5).
(7) TORQUE the clamp (1) to between 1.120 and 0.916 m.daN (99.12 and 81.06 lbf.in )
.
(8) Tighten the clamp (4).
5. Close-up(1) Remove the blanking plugs from the disconnected line ends.
(2) Clean the component interfaces and the adjacent area.
(3) Make sure that the parts retained from the removed component are clean and in the correct condition.
(4) Put the recirculation check valve (2) in position in the flange (3).
(5) Put the flange (3) (together with the recirculation check valve (2)) in position in the sleeve (5).
NOTE: The center line of the recirculation check-valve hinge must be in a vertical position.
(6) Install the clamp (1). (7) TORQUE the clamp (1) to between 1.120 and 0.916 m.daN (99.12 and 81.06 lbf.in )
. (8) Tighten the clamp (4).
NOTE: The end of the sleeve (5) must be within the painted marks on the flange (3).
Subtask 21-21-42-410-050-A
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel(s) removed from partition FR34 (Ref. AMM TASK 25-54-12-400-001):
(a) FOR [4020HM] (RECIRC CHECK VALVE 1)
(b) FOR [4021HM] (RECIRC CHECK VALVE 2)
(3) Remove the access platform(s).
(4) Close FWD cargo-compartment door 825 (Ref. AMM TASK 52-30-00-860-002).
(5) Remove the WARNING NOTICE(S).
Subtask 21-21-42-865-052-A (1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the access panel(s) removed from partition FR34 (Ref. AMM TASK 25-54-12-400-001):
(a) FOR [4020HM] (RECIRC CHECK VALVE 1)
(b) FOR [4021HM] (RECIRC CHECK VALVE 2)
(3) Remove the access platform(s).
(4) Close FWD cargo-compartment door 825 (Ref. AMM TASK 52-30-00-860-002).
(5) Remove the WARNING NOTICE(S).
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):
Subtask 21-21-42-862-050-A | PANEL | DESIGNATION | FIN | LOCATION |
|---|---|---|---|
| ** ON A/C ALL | |||
| FOR FIN: 4020HM (RECIRC CHECK VALVE 1) | |||
| 122VU | AIR COND/RECIRC FAN/L/CTL | 2HG | X20 |
| 122VU | AIR COND/RECIRC FAN/L/SPLY | 1HG | X18 |
| FOR FIN: 4021HM (RECIRC CHECK VALVE 2) | |||
| 122VU | AIR COND/RECIRC FAN/R/CTL | 11HG | W20 |
| 122VU | AIR COND/RECIRC FAN/R/SPLY | 3HG | W18 |
Recirculation Check Valve 4020HM (4021HM).